- 202 -
[
IX
Troubleshooting ]
Error
Code
Error definition and error detec-
tion method
Check method and remedy
6602
Transmission processor hard-
ware error
Although "0" was surely trans-
mitted by the transmission pro-
cessor, "1" is displayed on the
transmission line.
The address/attribute ap-
peared on the display on
the remote controller in-
dicates the controller
where an error oc-
curred.
(1) When the wiring work of or the polarity of either the indoor or heat source
transmission line is performed or is changed while the power is on, the trans-
mitted data will collide, the wave shape will be changed, and an error will be
detected.
(2) Grounding fault of the transmission line
(3) When grouping the indoor units that are connected to different heat source
units, the male power supply connectors on the multiple heat source units are
connected to the female power supply switch connector (CN40).
(4) When the power supply unit for transmission lines is used in the system con-
nected with MELANS, the male power supply connector is connected to the
female power supply switch connector (CN40) on the heat source unit.
(5) Controller failure of the source of the error
(6) When the transmission data is changed due to the noise on the transmission
line
(7) Voltage is not applied on the transmission line for centralized control (in case
of grouped indoor units connected to different heat source units or in case of
the system connected with MELANS)
Check method and remedy
NO
Tightly reconnect the male power
supply connector to the female
power supply switch connector (CN40).
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
Is the transmission line work
performed while the power is on?
Check the power source of the indoor unit.
208 / 230V?
Check the transmission line work is performed
and the shielded wire is treated properly.
Grounding fault or does the shielded
wire contact with the transmission line?
System ?
Faulty power source work
Improper transmission line work
Turn off the power source of heat source
/indoor units, and turn them on again.
NO
Investigation into the
transmission line noise
Noise exist?
Controller failure of the
source of the error
*For the investigation method, follow
<Investigation method of transmission wave shape/noise>
Investigation into the
cause of the noise
Correct the error.
System with the power supply
unit for transmission lines
Is the male power supply connector
connected to the female power supply
switch connector (CN40) on only one
of the heat source unit?
Is the male power supply connector
connected to the female power supply
switch connector (CN40) ?
Confirm that the power supply
connector on the heat source
unit is not plugged into CN40.
Confirm that the power supply
connector on the heat source
unit is not plugged into CN40.
Disconnect the male
power supply on
CN40 and connect it to CN41
Single-heat source-unit system
Multiple-heat source-unit system
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...