- 125 -
[
VII
Control ]
2. Function of the switch (Indoor unit)
(1) Dipswitches
[SW1,3]
Switch
Function
Function according to switch setting
OFF
ON
Switch setting timing
OFF
ON
Notes
SW1
SW3
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
Room temperature
detection position
Clogged filter detection
Filter check reminder time setting
Outside air intake
Remote display option
Humidifier control
Self-recovery after power failure
Fan speed setting for
Heating Thermo-OFF
Power source start-stop
Unit model selection
Louver
Vane
Vane swing function
-
Vane angle limit setting
for cooling operation
Initial vane position
Heating 4-deg up
Indoor unit inlet
100h
Disabled
Fan output
2500h
Enabled
Thermo-ON signal
Built-in sensor on
the remote controller
Available
During heating operation
According to the
SW1-7 setting
Heat pump
Always on while in the heating mode
Fan speed setting for
Heating Thermo-OFF
Very Low
Low
Preset speed
Cooling only
Enabled
Enabled
Disabled
Disabled
Enabled
Valid
Not available
Available
Not available
Available
Not available
Not available
Available
-
-
-
-
-
-
-
-
Downblow B,C
Horizontal
While the unit is stopped
(Remote controller OFF)
Always set to OFF on PKFY-NAMU model units
Set to ON (built-in sensor on the remote controller)
on All Fresh (PEFY-NMHU-E-F) model units
Applicable to All Fresh model units
(PEFY-NMHU-E-F) only
Always set to OFF on PKFY-NAMU model units
PLFY-NLMU model only
Set to OFF on floor-standing (PFFY) type units
Note 1. Settings in the shaded areas are factory settings.
Note 2. On a system with a G-50 connection, set Dip SW 1-9 and 1-10 to ON to control input/output using the PLC for general equipment. With these settings made, the power
start/stop function will be disabled. Set Dip SW 1-5 to ON to use the auto-recovery after power failure function.
Refer to the table below for the factory setting of the switches whose factory settings are not indicated by the shaded cells.
Always set to Downblow B or C on
PKFY-NAMU model units
Disabled
Disabled
Model
PLFY
PMFY
PDFY
PEFY
PCFY
PKFY
PFFY
-NAMU
-NLMU
-NBMU
-NMU
-NMLU
-NMHU
-NMHU-F
-NGMU
-NAMU
-NGMU
-NFMU
-NEMU
-NRMU
SW1
3
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
6
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
7
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
SW3
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
4
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
Note 3. Setting timing for the DIP SW 1, 2, 3, and 4 is when the unit is stopped (remote controller OFF). It is not necessary to power reset.
Note 4. When both SW1-7 and 1-8 are set to ON, the fan stops while the unit is under the Heating Thermo-OFF conditions.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...