- 147 -
[
VII
Control ]
(3) Dry operation
Dry operation
Test run mode
ON
Suction temperature
18 C[64 F]
*Note 1
*Note 2
YES
YES
NO
NO
4-way valve OFF
1. Heat source unit (compressor) intermittent operation
2. Indoor unit fan intermittent operations
(Synchronized with the compressor :
low speed, OFF operations)
Normal operation
Thermostat ON
Thermostat ON
1. Indoor unit fan stop
2. Inverter output 0Hz
3. Indoor LEV, LEV1 Fully closed
4. Solenoid valve OFF
5. 52C OFF
[1] or [2]
*Note 1. When the indoor unit inlet temperature exceeds 18 C [64 F], the heat source unit (compressor) and the indoor unit fan
start the intermittent operation simultaneously. When the indoor unit inlet temperature becomes 18 C [64 F] or less,
the fan always runs (at low speed). The heat source unit, the indoor unit, and the solenoid valve operate in the same
way as they do in the cooling operation when the compressor is turned on.
*Note 2. Thermostat is always kept on during test run mode, and indoor and heat source unit intermittent operation (ON) time
is a little longer than that of normal operation.
Unit in the stopped state
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...