- 55 -
[
II
Restrictions ]
(2) Header branching
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Total pipe length
A+a+b+c+d+e+f
300 [984] or less
Total pipe length (L) from the heat source unit to
the farthest indoor unit
A+f
150 [492] or less
Total pipe length from the first branch to the far-
thest indoor unit ( )
f
40 [131] or less
Height
difference
Between indoor and
heat source units
Heat source unit above
indoor unit
H
50 [164] or less
Heat source unit below
indoor unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
L
H
H'
A
a
b
c
d
h
e
f
5
1
2
3
4
6
cap
Note:Pipes from the header may not be re-branched.
First branch
Indoor Indoor
Indoor Indoor Indoor
Indoor
Heat source unit