Note1 BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the board.
Note2 Check method of fully open state or fully closed state of LEV
1) Check LEV opening (pulse) on the self-diagnosis LED (Heat source unit control board SW1).
Full open: 2000 pulses
Fully closed: 110 pulses (In the case of heating-only mode, however, the pulse may become 110 or more.)
2) When LEV is fully open, measure the temperature at the upstream and downstream pipes of LEV, and make
sure that there is no temperature difference.
3) When LEV is fully closed, check that there is no refrigerant flowing sound.
Note3 Refer to the chart below to judge LEV opening controlled by the values of the differential pressure and of the super-
heat. (BC controller LEV basic operation characteristic)
Phenomena
Cooling-only
Cooling-main
Heating only
Heating main
Non-cooling
SH12 small, SC11 small
SH16 small, branch pipe
SC small
BC controller sound
Non-cooling and non-heat-
ing
SH12 small, SC11 small
SH16 large, but branch
pipe SC small
BC controller sound PHM
large
Indoor heating SC small
PHM large
Non-cooling
Indoor heating SC small
PHM large
Part
Malfunction
mode
Operation
mode
Content
Standards of judgment on
unit stable operation
NU-
G,GA
(Main)
LEV1
Inclined to
close
Heating only
Heating-
main
Cooling-
main
Difference between high
pressure (P1) and interme-
diate pressure (P3) is large.
0.3 - 0.4MPa
[44 - 58psi]
Inclined to
open
Difference between high
pressure (P1) and interme-
diate pressure (P3) is
small.
LEV3
Inclined to
close
Cooling-only
Cooling-
main
SH12 is large.
SH12 < 20K [36°F]
Heating only
Heating-
main
Difference between high
pressure (P1) and interme-
diate pressure (P3) is
small.
0.3 - 0.4MPa
[44 - 58psi]
Inclined to
open
Cooling-only
Cooling-
main
SC16 and SH12 are small.
SC16 > 3K [5°F]
SH12 > 3K [5°F]
Heating only
Heating-
main
Difference between high
pressure (P1) and interme-
diate pressure (P3) is large.
0.3 - 0.4MPa
[44 - 58psi]
NU-GB
(Sub)
LEV3a
Inclined to
close
Cooling-only
Cooling-
main
SH22 is large.
SH22 < 20K [36°F]
Inclined to
open
Cooling-only
Cooling-
main
SH22 is small.
SH22 > 3K [5°F]
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...