background image

124A

LEGACY

t

LINE 14 AIR CONDITIONER

WITH PURON

r

REFRIGERANT

1--1/2 TO 5 TONS (SIZES 018 TO 060)

PRODUCT DATA

TM

the environmentally sound refrigerant

Bryant Air Conditioners with Puron

r

refrigerant provide a

collection of features unmatched by any other family of

equipment. The 124A has been designed utilizing Bryant’s Puron
refrigerant. The environmentally sound refrigerant allows you to

make a responsible decision in the protection of the earth’s ozone
layer.
As an Energy Star

r

Partner, Bryant Heating & Cooling has

determined that this product meets the Energy Star

r

guidelines

for energy efficiency. Refer to the combination ratings in the

Product Data for system combinations that meet Energy Star

r

guidelines.

NOTE

:

Ratings contained in this document are subject to

change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.

INDUSTRY LEADING

FEATURES / BENEFITS

Efficiency

S

14 SEER / 11.5 -- 12.0 EER

S

Microtube Technology

t

refrigeration system

S

Indoor air quality accessories available

Sound

S

Sound level as low as 72 dBA

S

Compressor sound blanket

Comfort

S

System supports Thermidistat

t

or standard thermostat

controls

Reliability

S

Puron

r

refrigerant -- environmentally sound, won’t

deplete the ozone layer and low lifetime service cost.

S

Front--seating service valves

S

Scroll compressor

S

Internal pressure relief valve

S

Internal thermal overload

S

Low pressure switch

S

High pressure switch

S

Filter drier

S

Balanced refrigeration system for maximum reliability

Durability

DuraGuard

t

protection package:

S

Solid, Durable sheet metal construction

S

Steel louver coil guard

S

Baked--on, complete outer coverage, powder paint

S

Color matched ceramic coated screws

Applications

S

Long--line -- up to 250 feet (76.2 m) total equivalent
length, up to 200 feet (60.96 m) condenser above

evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)

S

Low ambient (down to --20

_

F/--28.9

_

C) with accessory

kit

Summary of Contents for LEGACY 124A

Page 1: ...DUSTRY LEADING FEATURES BENEFITS Efficiency S 14 SEER 11 5 12 0 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 72 dBA S Compressor sound blanket Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete the ozone layer and low lifetime servic...

Page 2: ...d efficiency Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life STANDARD FEATURES FEATURES Unit Size Series 018 C 024 D 030 D 036 C 042 D 048 C 060 C Puron Refrigerant X X X X X X X Maximum SEER Rating 15 5 16 0 16 0 16 0 16 0 15 0 14 5 Scro...

Page 3: ... ft 60 96 m when outdoor unit is above indoor unit and up to 80 ft 24 38 m when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Longline Application Guideline for required piping and system modifications Also refer to the table below for the vapor tube diameters based on the total length to minimize the cooling capacity loss Unit Nomi...

Page 4: ...R START X X X X X X X x Accessory See Accessory Usage Guideline for other accessories needed for low ambient cooling applications THERMOSTATS THERMOSTAT SUBBASE PKG DESCRIPTION T6 PRH 01 Programmable Thermidistat T6 NRH 01 Non programmable Thermidistat T2 PAC 01 Legacy Series Programmable AC Stat T2 NAC 01 Legacy Series Non programmable AC Stat TSTATBBPRH01 B Thermidistat Control Programmable Non ...

Page 5: ...minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Cycle Protector The cycle protector is designed to prevent compressor short cycling This control provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason including power out...

Page 6: ...the superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter tubes and external equalizer tube Hard shut off types are available NOTE When using a hard shut off TXV with single phase reciprocating compressors a Compressor Start Assist Capacitor and Relay is required Usage Guideline Required to achieve ARI ratings in certain equipment combinations Refer to combination rati...

Page 7: ...licable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors ...

Page 8: ...8 DIMENSIONS ENGLISH 124A ...

Page 9: ...9 DIMENSIONS SI 124A ...

Page 10: ...arious examples Wall Wall Wall Wall 24 Service 6 152 4 mm 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm A07833 124A ...

Page 11: ...018 C FE4ANF002 UI 18200 13 20 16 00 1 3047903 124ANA018 C FF1ENP018 17800 11 20 13 50 1 3047904 124ANA018 C FF1ENP024 18000 11 20 13 50 1 3047905 124ANA018 C FV4BNF002 18200 13 20 16 00 1 3047900 124ANA018 C FX4CNF018 18000 13 00 15 50 1 3047901 124ANA018 C FX4CNF024 18300 13 00 15 50 1 3047898 124ANA018 C FY4ANF018 17800 11 20 13 50 1 3047899 124ANA018 C FY4ANF024 17900 11 20 13 50 1 3047906 124...

Page 12: ...V042060 23200 13 00 15 50 1 3047962 124ANA024 D CSPH 2412A 355 A C AV042080 23200 13 00 15 50 1 3047963 124ANA024 D CSPH 2412A 355 A C AV060080 23000 13 00 15 50 1 3047964 124ANA024 D CSPH 2412A 355 A C AV060100 23200 13 00 15 50 1 3047965 124ANA024 D CSPH 2412A 355 A C AV060120 23200 13 00 15 50 1 3047959 124ANA024 D CSPH 2412A TDR 23400 12 00 14 00 1 3047914 124ANA024 D CSPH 3012A 313 AV024045 2...

Page 13: ...3617A 355 A C AV042060 28800 12 50 15 00 1 3048051 124ANA030 D CNPH 3617A 355 A C AV042080 28800 12 50 15 00 1 3048052 124ANA030 D CNPH 3617A 355 A C AV060080 28800 12 50 15 00 1 3048053 124ANA030 D CNPH 3617A 355 A C AV060100 28600 12 50 15 00 1 3048054 124ANA030 D CNPH 3617A 355 A C AV060120 28800 12 50 15 00 1 3048048 124ANA030 D CNPH 3617A TDR 29000 11 70 14 00 1 3048024 124ANA030 D CNPV 3014A...

Page 14: ...15 00 1 3048128 124ANA036 C CAP 3617A TDR 35400 11 50 14 00 1 3048101 124ANA036 C CAP 3621A 313 AV048090 35600 12 75 15 00 1 3048102 124ANA036 C CAP 3621A 313 AV060110 35800 13 00 15 25 1 3048135 124ANA036 C CAP 3621A 315 A J AV060110 35200 13 00 15 00 1 3102044 124ANA036 C CAP 3621A 353AAV060100 35400 12 50 15 00 1 3048132 124ANA036 C CAP 3621A 355 A C AV042080 35000 12 50 14 50 1 3048133 124ANA0...

Page 15: ...AV060100 35400 12 50 15 00 1 3048163 124ANA036 C CSPH 3612A 355 A C AV042040 35000 12 50 15 00 1 3048162 124ANA036 C CSPH 3612A TDR 35400 12 00 14 00 1 3048122 124ANA036 C CSPH 4212A 313 AV024045 36000 12 20 14 50 1 3048123 124ANA036 C CSPH 4212A 313 AV048070 36000 12 50 15 00 1 3048124 124ANA036 C CSPH 4212A 313 AV048090 36000 13 00 15 25 1 3048125 124ANA036 C CSPH 4212A 313 AV060110 36000 13 00 ...

Page 16: ...4821A 315 A J AV060110 40000 12 50 15 00 1 3048271 124ANA042 D CNPH 4821A 315 A J AV066135 40000 12 50 15 00 1 3048272 124ANA042 D CNPH 4821A 315 A J AV066155 40000 13 00 15 50 1 3102092 124ANA042 D CNPH 4821A 353AAV048080 40000 12 20 14 50 1 3102093 124ANA042 D CNPH 4821A 353AAV060100 40000 12 50 15 00 1 3102094 124ANA042 D CNPH 4821A 353AAV060120 40000 12 50 15 00 1 3048262 124ANA042 D CNPH 4821...

Page 17: ...X4CN B F 048 41500 13 00 15 00 1 3048298 124ANA042 D FY4ANF042 40000 11 70 13 50 1 3048299 124ANA042 D FY4ANF048 40500 11 70 13 50 1 3048309 124ANA048 C CAP 6024A TDR 48000 11 50 14 00 1 3048310 124ANA048 C CAP 4817A 313 AV048070 46500 11 00 13 00 1 3048338 124ANA048 C CAP 4817A 315 A J AV048090 46000 11 50 14 20 1 3102102 124ANA048 C CAP 4817A 353AAV048080 47000 11 70 13 50 1 3048337 124ANA048 C ...

Page 18: ...48378 124ANA048 C CSPH 6012A 315 A J AV048090 46500 12 00 14 50 1 3102119 124ANA048 C CSPH 6012A 353AAV048080 47000 12 00 14 00 1 3102120 124ANA048 C CSPH 6012A 353AAV060100 47000 12 20 14 50 1 3102121 124ANA048 C CSPH 6012A 353AAV060120 47000 12 20 14 50 1 3048377 124ANA048 C CSPH 6012A 355 A C AV060080 46000 12 00 14 20 1 3048376 124ANA048 C CSPH 6012A TDR 47000 11 50 14 00 1 3048383 124ANA048 C...

Page 19: ...06 59000 12 50 14 50 1 3048422 124ANA060 C FX4CN B F 060 59500 12 00 14 00 1 3048421 124ANA060 C FY4ANB060 59000 11 50 13 50 1 Tested combination EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use either the accessory T...

Page 20: ... 75 15 33 15 33 1 95 14 37 14 37 2 18 57 13 9 18 63 18 63 1 24 17 86 17 86 1 39 17 06 17 06 1 56 16 22 16 22 1 75 15 33 15 33 1 95 14 37 14 37 2 18 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CAP 2414A 1 00 1 00 CAP 1814A 0 99 1 02 CAP 2417A 1 00 1 00 CNPF 2418A 1 00 1 00 CNPH 2417A 1 00 1 00 CNPV 1814A 0 99 1 02 CNPV 2414A 1 00 1 00 CNPV 2417A 1 00 1 00 CSPH 2412A 1 00 0 96 FE4ANF002 1 01 0...

Page 21: ...5 A J AV048090 CNPH 3017A 1 00 0 89 315 A J AV048090 CNPV 2417A 0 99 0 89 315 A J AV048090 CNPV 3017A 1 00 0 89 315 A J AV048090 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 2412A 1 00 0 90 315 A J AV048090 CSPH 3012A 1 01 0 89 315 A J AV048090 CNPH 2417A 0 99 0 93 315 A J AV060110 CNPH 3017A 1 00 0 90 315 A J AV060110 CSPH 2412A 1 00 0 90 315 A J AV060110 CSPH 3012A 1 01 0 91 315 A J AV...

Page 22: ...0 99 0 93 315 A J AV048090 CNPV 3017A 0 99 0 93 315 A J AV048090 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 3617A 0 99 0 93 315 A J AV048090 CSPH 3012A 1 00 0 94 315 A J AV048090 CSPH 3612A 1 00 0 90 315 A J AV048090 CAP 3621A 1 00 0 90 315 A J AV060110 CNPH 3017A 1 00 0 94 315 A J AV060110 CNPH 3617A 1 00 0 94 315 A J AV060110 CNPV 3621A 1 00 0 94 315 A J AV060110 CSPH 3012A 1 00 0 94...

Page 23: ...070 CAP 3617A 1 01 0 94 313 AV048070 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 3017A 1 00 0 94 313 AV048070 CNPH 3617A 1 00 0 94 313 AV048070 CNPV 3017A 1 00 0 94 313 AV048070 CNPV 3617A 1 00 0 94 313 AV048070 CSPH 3012A 1 00 0 94 313 AV048070 CSPH 3612A 1 01 0 95 313 AV048070 CAP 3621A 1 01 0 91 313 AV048090 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 3017A 1 00 0 94 313 A...

Page 24: ...48090 CAP 3621A 0 98 0 91 315 A J AV060110 CAP 4221A 0 99 0 91 315 A J AV060110 CNPV 3621A 0 98 0 94 315 A J AV060110 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 4221A 0 99 0 91 315 A J AV060110 CAP 4224A 0 99 0 91 315 A J AV066135 CNPH 4221A 0 98 0 91 315 A J AV066135 CNPH 4221A 0 98 0 91 315 A J AV066155 CAP 3617A 0 99 0 95 353AAV036040 CNPH 3617A 0 98 0 94 353AAV036040 CNPH 4221A 0 9...

Page 25: ...APACITY POWER FURNACE MODEL CAP 3621A 1 00 0 92 313 AV060110 CAP 4221A 1 01 0 93 313 AV060110 CNPH 3617A 0 99 0 95 313 AV060110 CNPH 4221A 1 00 0 92 313 AV060110 CNPV 3621A 0 99 0 95 313 AV060110 CNPV 4221A 1 00 0 92 313 AV060110 CSPH 3612A 1 00 0 92 313 AV060110 CSPH 4212A 1 01 0 93 313 AV060110 See notes on page 29 124A ...

Page 26: ...1A 0 99 0 97 315 A J AV060110 CNPH 4821A 1 00 0 96 315 A J AV060110 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 4221A 0 99 0 97 315 A J AV060110 CNPV 4821A 1 00 0 96 315 A J AV060110 CSPH 4212A 0 99 0 97 315 A J AV060110 CSPH 4812A 1 00 0 96 315 A J AV060110 CAP 4224A 0 99 0 95 315 A J AV066135 CAP 4824A 1 00 0 96 315 A J AV066135 CNPH 4221A 0 99 0 95 315 A J AV066135 CNPH 4821A 1 00 0 ...

Page 27: ...0 99 0 95 313 AV048090 CAP 4821A 1 00 0 94 313 AV048090 CNPH 4221A 0 99 0 95 313 AV048090 CNPH 4821A 1 00 0 92 313 AV048090 CNPV 4221A 0 99 0 95 313 AV048090 CNPV 4821A 1 00 0 92 313 AV048090 CSPH 4212A 1 00 0 92 313 AV048090 CSPH 4812A 1 01 0 93 313 AV048090 CAP 4221A 0 99 0 95 313 AV060110 CAP 4821A 1 00 0 92 313 AV060110 CNPH 4221A 0 99 0 95 313 AV060110 CNPH 4821A 1 01 0 93 313 AV060110 COOLIN...

Page 28: ...A 0 97 0 93 315 A J AV048090 CAP 4821A 0 97 0 93 315 A J AV060110 CAP 6021A 0 98 0 94 315 A J AV060110 CNPV 4821A 0 96 0 92 315 A J AV060110 CAP 4824A 0 98 0 94 315 A J AV066135 CAP 6024A 1 00 0 96 315 A J AV066135 CNPV 4824A 0 96 0 92 315 A J AV066135 CNPV 6024A 0 97 0 93 315 A J AV066135 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CAP 4824A 0 98 0 94 315 A J AV066155 CAP 6024A 1 00 0 92 31...

Page 29: ... 97 315 A J AV060110 CSPH 6012A 0 97 0 97 315 A J AV060110 CAP 6024A 0 98 0 98 315 A J AV066135 CNPH 6024A 0 97 0 97 315 A J AV066135 CNPV 6024A 0 97 0 97 315 A J AV066135 CSPH 6012A 0 97 0 97 315 A J AV066135 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CAP 6024A 0 98 0 98 315 A J AV066155 CNPH 6024A 0 98 0 98 315 A J AV066155 CNPV 6024A 0 98 0 98 315 A J AV066155 CSPH 6012A 0 98 0 98 315 A ...

Page 30: ... 12 78 TCG 33 40 31 70 30 00 28 30 26 50 24 70 22 90 20 90 SDT 72 60 81 80 90 90 100 10 109 30 118 60 127 80 137 10 KW 1 01 1 15 1 31 1 49 1 69 1 92 2 16 2 43 124ANA030 D 30 1 11 TCG 27 40 25 90 24 50 22 90 21 30 19 70 18 00 16 20 SDT 68 50 77 80 87 20 96 60 106 00 115 40 124 90 134 30 KW 1 25 1 43 1 63 1 85 2 09 2 35 2 63 2 93 35 1 67 TCG 30 20 28 60 27 00 25 30 23 60 21 90 20 00 18 00 SDT 69 70 ...

Page 31: ...18 40 127 50 136 50 KW 2 14 2 43 2 76 3 12 3 53 3 97 4 45 4 97 45 7 22 TCG 60 10 57 00 53 90 50 70 47 30 43 80 40 10 36 20 SDT 74 60 83 50 92 50 101 50 110 50 119 50 128 50 137 40 KW 2 15 2 44 2 77 3 13 3 54 3 98 4 46 4 98 50 10 0 TCG 65 60 62 20 58 80 55 20 51 60 47 70 43 70 39 40 SDT 76 20 85 10 93 90 102 90 111 80 120 70 129 60 138 30 KW 2 16 2 45 2 78 3 14 3 55 3 99 4 47 4 99 55 12 78 TCG 71 3...

Page 32: ...gs Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber vibration isolators Compressor will be covered with a sound absorbing blanket Condenser Coil Condenser coil will be air cooled Coil will be con...

Reviews: