- 60 -
[
II
Restrictions ]
(2) Between BC controller and indoor unit (Parts a, b, c, d, and e)
(3) Between main BC controller and sub BC controller (Part C)
Select the proper size pipes for the main BC controller based on the total capacity of the indoor units that are connected
to both of the sub BC controllers, and for the sub BC controller, on the total capacity of the indoor units that are con-
nected to each sub BC controller.
(Note) Use the piping that is specified in Section "[3] Piping Materials" under "Read Before Servicing".
Unit: mm [in]
Operation
Indoor unit
06,08,12,15,18
24,27,30,36,48
72
96
Refrigerant pipe
size
Liquid
pipe
ø6.35 [1/4"]
ø9.52 [3/8"]
Gas
pipe
ø12.7 [1/2"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.2 [7/8"]
Connection to in-
door unit (Flare
connection for all
models)
Liquid
pipe
ø6.35 [1/4"]
ø9.52 [3/8"]
Gas
pipe
ø12.7 [1/2"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.2 [7/8"]
Unit: mm [in]
Operation
Indoor unit
-P72
P73-P108
P109-P126
Refrigerant pipe
size
(Brazed connec-
tion for all mod-
els)
Liquid pipe
ø9.52 [3/8"]
ø12.7 [1/2"]
High-pres-
sure gas
pipe
ø15.88 [5/8"]
ø19.05 [3/4"]
Low-pres-
sure gas
pipe
ø19.05 [3/4"]
ø22.2 [7/8"]
ø28.58 [1-1/8"]
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...