- 288 -
[
IX
Troubleshooting ]
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
Note1 SVA, SVB, SVC
SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.
SVM,SVM2
SVM1 and SVM2 turn on or off according to the operation mode.
Note2 SVA, SVB, SVC
Measure the temperature at the upstream and downstream pipes and of SVA.
Measure the temperature at the upstream and downstream pipes and of SVA.
4. BC controller transformer
*Before measuring the resistance, pull out the connector.
Mode
Cooling
Heating
Stopped
Fan
Port
SVA
ON
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
SVC
ON
OFF
OFF
ON
Operation
mode
Cooling only
Cooling main
Heating only
Heating main
Stopped
SVM1
ON
Pressure differ-
ential control
OFF or ON
OFF
OFF
OFF
SVM2
OFF
OFF
Pressure differ-
ential control
OFF or ON
Pressure dif-
ferential con-
trol
OFF or ON
OFF
Normal
Abnormal
CNTR(1) - (3)
about 58 ohm.
Open-phase or shorting
CN03(1) - (3)
about 16 ohm.
CNTR
CN03
BC controller control board
Red
White
Red
Red
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...