- 144 -
[
VII
Control ]
(2) Heat source unit (cooling and heating modes)
*Note 1.
For about 3 minutes after power on, search for the indoor unit address, for the remote controller address,
and for the group information will start. During this, "HO" / "PLEASE WAIT" blinks on the display of the remote
controller. When the indoor unit to be controlled by the remote controller is missing, "HO" / "PLEASE WAIT" keeps
blinking on the display of the remote controller even after 3 or more minutes after power on.
*Note 2.
The system may go into the error mode on either the indoor unit or the heat source unit side. The heat source stops
only when all of the connected indoor units are experiencing problems. The operation of even a single indoor unit will
keep the heat source unit running. The error will be indicated on the LED display.
*Note 3.
The heat source unit operates according to the operation mode commanded by the indoor unit. However, when the
heat source unit is running a cooling operation, come of the operating indoor units will stop, or the operation of these
indoor units will be prohibited even when the indoor unit mode is switched from fan mode to heating mode.
This also applies when the heat source unit is running a heating operation.
Start
Breaker
turned on
Operation
command
Error stop
Error display on the
heat source unit LED
Error command to
indoor unit
Operation
mode
Operation
mode
Error mode
52C1 ON
*Note 1
*Note 3
*Note 2
YES
YES
YES
YES
NO
NO
NO
NO
"HO" / "PLEASE WAIT" blinks on
the remote controller
Operation command to indoor unit To [1].
Cooling only,Heating only,
Mixture of units in cooling and heating
1. Protection function self-holding cancelled.
2. LEV1 fully closed.
Normal operation
1. 52C OFF
2. Inverter output 0Hz
3. All solenoid valves OFF
Refer to Cooling/Dry
Operation 2-(1) and 2-(3)
Refer to heating
Operation 2-(2).
2
From indoor unit
Error
Unit in the stopped state
Self-holding of
protection function
Indoor units
registered to the
remote controller
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...