- 109 -
[
VI
Refrigerant Circuit ]
[2] Principal Parts and Functions
1. Heat source unit
(1) PQHY
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check
method
Compres-
sor
MC1
(Comp1)
Adjusts the amount of circulating
refrigerant by adjusting the oper-
ating frequency based on the op-
erating pressure data
Low-pressure shell scroll
compressor
Wirewound resistance
10°C[50°F] :0 .155ohm
20°C[68°F] : 0.161ohm
30°C[86°F] : 0.167ohm
High
pressure
sensor
63HS 1. Detects
high
pressure
2. Regulates frequency and pro-
vides high-pressure protection
Low
pressure
sensor
63LS
1. Detects low pressure
2. Provides low-pressure protec-
tion
Pressure
switch
63H1
1. Detects high pressure
2. Provides high-pressure pro-
tection
4.15MPa[601psi] OFF setting
Pressure
0~4.15 MPa [601psi]
Vout 0.5~3.5V
0.071V/0.098 MPa [14psi]
Pressure [MPa]
=1.38 x Vout [V]-0.69
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63HS
1
1 2 3
2
3
Pressure
0~1.7 MPa [247psi]
Vout 0.5~3.5V
0.173V/0.098 MPa [14psi]
Pressure [MPa]
=0.566 x Vout [V] - 0.283
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63LS
1
1 2 3
2
3
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...