- 240 -
[
IX
Troubleshooting ]
-
(2) Grouping of units in a system with multiple heat source units
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Heat
source
unit
(OC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at
BC trans-
mission to
OC
Same cause as that for system with
one heat source unit
Same remedy as that for system with one
heat source unit
BC control-
ler
(BC)
M-NET re-
mote con-
troller (RC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to BC
Same cause as that for system with
one heat source unit
Same remedy as that for system with one
heat source unit
Indoor
unit
(IC)
M-NET re-
mote con-
troller (RC)
No ac-
knowl-
edgement
(ACK) at
RC trans-
mission to
IC
(1) Same causes as (1) - (5) for sys-
tem with one heat source unit
(2) Disconnection or short circuit of
the transmission line for the heat
source unit on the terminal block
for centralized control line con-
nection (TB7)
(3) When multiple heat source units
are connected and the power
source of one of the heat source
units has been shut off.
(4) The male power supply connec-
tor of the heat source unit is not
connected to the female power
supply switch connector (CN40).
(5) The male power supply connec-
tors on 2 or more heat source
units are connected to the fe-
male power supply switch con-
nector (CN40) for centralized
control.
If an error occurs, after the unit runs
normally once, the following causes
may be considered.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of con-
nected units (7102)
Address setting error (7105)
1) Turn off the power sources of the heat
source and indoor units for 5 or more
minutes, and turn them on again. If the
error is accidental, the will run normal-
ly.If not, check the cause 2).
2) Check the causes of (1) - (5). If the
cause is found, correct it. If no cause is
found, check 3).
3) Check the LED displays for trouble-
shooting on other remote controllers
whether an error occurs.
If an error is found,
-> If an error is found, check the check
code definition, and correct the error.
If no error is found,
-> Indoor unit board failure
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...