- 187 -
[
IX
Troubleshooting ]
2134
Abnormal wa-
ter tempera-
ture
1.If an inlet water tem-
perature of 5°C [41
°F] or below, or
50°C[122 °F] or above
is detected (first de-
tection), the heat
source unit comes to a
stop, goes into 3-min.
restart prevention
mode, and restarts af-
ter three minutes.
2.If an inlet water tem-
perature of 5°C [41
°F] or below, or
50°C[122°F] or above
is detected again (sec-
ond detection) within
thirty minutes of the
first detection (See
item 1 above), the
heat source unit
comes to an abnormal
stop and displays the
code "2134."
3.If an inlet water tem-
perature of 5°C[41 °F]
or below, or 50°C[122
°F] or above is detect-
ed again (second de-
tection) more than
thirty minutes after the
first detection (See
item 1 above), it is
considered as the first
detection, and the
same sequence of op-
eration as the one in
item 1 above is fol-
lowed.
(1) Heat source water pump
failure
(2) Problems with the cooling
tower or heating device
(3) Dirty or clogged water heat
exchanger
(4) Thermistor failure (TH6)
(5) Failure of the thermistor in-
put circuit on the control
board
(6) Thermistor installation
problem (TH6)
Error Code
Error definition and error
detection method
Cause
Check method and remedy
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...