- 245 -
[
IX
Troubleshooting ]
(4) Errors that are not limited to a particular system
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote control-
ler indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Address
which
should not
be existed
-
-
(1) Although the address of M-NET
remote controller has been
changed after the group is set
using M-NET remote controller,
the indoor unit is keeping the
memory of the previous ad-
dress.
The same symptom will appear
for the registration with SC.
(2) Although the address of LOSS-
NAY has been changed after the
interlock registration of LOSS-
NAY is made using M-NET re-
mote controller, the indoor unit is
keeping the memory of the pre-
vious address.
Delete unnecessary information of non-ex-
isting address which some indoor units
have.
Use either of the following two methods for
deletion.
1) Address deletion by M-NET remote
controller
Delete unnecessary address informa-
tion using the manual setting function of
M-NET remote controller. Refer to this
service handbook "4.[2]. Group settings
and interlock settings via the ME remote
controller 1. (3) Address deletion".
2) Deletion of connection information of
the heat source unit by the deleting
switch
Note that this switch deletes all the
group information set via M-NET re-
mote controller and all the interlock
information of LOSSNAY and the in-
door unit.
Turn off the power source of the heat
source unit, and wait for 5 minutes.
Turn on the dip switch (SW2-2) on the
heat source unit main board.
Turn on the power source of the heat
source unit, and wait for 5 minutes.
Turn off the power source of the heat
source unit, and wait for 5 minutes.
Turn off the dip switch (SW2-2) on the
heat source unit main board.
Turn on the power source of the heat
source unit.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...