- 217 -
[
IX
Troubleshooting ]
Error Code
Error definition and error
detection method
Cause
Check method and remedy
1102
Abnormal dis-
charge air tem-
perature
1.If the discharge tem-
perature of 120
°C[248°F] or more is
detected during the
above operation (the
first detection), the
heat source unit stops
once, turns to anti-re-
start mode for 3 min-
utes, and restarts after
3 minutes automati-
cally.
2.If the discharge tem-
perature of 120
°C[248°F] or more is
detected again (the
second detection)
within 30 minutes after
the second stop of the
heat source unit de-
scribed above, the
mode will be changed
to 3-minute restart
mode, then the heat
source unit will restart
in 3 minutes.
3.If the discharge tem-
perature of 120 °C
[248°F] or more is de-
tected (the third detec-
tion) within 30 minutes
after the stop of the
heat source unit de-
scribed above (re-
gardless of the first or
the second stop), the
heat source unit will
make an error stop,
and the error code
"1102" will be dis-
played.
4.If the discharge tem-
perature of 120 °C
[248°F] or more is de-
tected more than 30
minutes after the pre-
vious stop of the heat
source unit, the detec-
tion is regarded as the
first detection, and the
operation described in
step 1 above will start.
5.For 30 minutes after
the stop (the first stop
or the second stop) of
the heat source unit,
preliminary errors will
be displayed on the
LED display.
(1) Gas leak, gas shortage
Refer to the page on refrigerant
amount evaluation.
(2) Overload operation
Check operating conditions and op-
eration status of indoor/heat source
units.
(3) LEV failure on the indoor
unit
(4) BC controller LEV mal-
function
Cooling only : LEV3
Cooling main : LEV1,2,3
Heating only or heating
main : LEV3
Defrost : LEV3
(5) BC controller SVM1 and 2
malfunction
-> Cooling only
(6) BC controller SVA mal-
function
-> Cooling only or cooling
main
(7) BC controller SVB mal-
function
-> Heating only or heating
main
(8) Solenoid valve SV mal-
function (4a-4d): heating
only, heating main
Perform a heating operation and
check the operation.
Cooling: LEV on the indoor unit
LEV1,2,3
SVM1,2
SVA
Heating: LEV on the indoor unit
LEV3
SVB
SV4a - 4d
Refer to the page on trouble-
shooting LEV.
(9) Port address setting error. Confirm the port address of the in-
door unit.
(10) Closed ball valve
Confirm that the ball valve is fully
open.
(11) Insufficient heat source
water supply, heat source
water supply cutoff, dirty or
clogged water heat ex-
changer
-> Heating only or heating
main
Items (3)-(11) are caused
by a rise in the discharge
temperature due to a drop
in pressure.
Check for dirty or clogged water heat
exchanger
Check the heat source water pump
(12) Gas leak between low
and high pressures(4-way
valve failure, compressor
failure, solenoid valve SV1
failure)
Perform a cooling or heating opera-
tion and check the operation.
(13) Thermistor failure
(TH11)
Check the thermistor resistor.
(14) Input circuit failure on the
controller board thermistor
Check the inlet air temperature on
the LED monitor and check for con-
tact failure of the connector.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...