- 182 -
[
IX
Troubleshooting ]
[2] Responding to Error Display on the Remote Controller
-1- PQHY
1. Mechanical system
Refer to section -7-"Inverter " under part [4] "Trouble shooting principal parts" for error codes related to the inverter.
Error Code
Error definition and error
detection method
Cause
Check method and remedy
0403
Serial commu-
nication error
Serial communication er-
ror between the main
board and the INV board
on the compressor, and
between the main board
and the inverter board
Detail code 01:
Between the main board
and the compressor INV
board
(1) Faulty wiring
Check the connection between the
Main board connector CNRS3B and
compressor INV board connector
CNRS1, and check connector con-
nections.
(2) Inverter address switch
setting error
Check the setting for SW2-1 on the
inverter board on the compressor.
(3) Compressor INV board
failure
Replace the compressor INV board
if problem persists after power reset.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...