IX
Troubleshooting ]
- 128 -
HWE15070
GB
DCCT sensor/circuit fault
●DCCT sensor fault
●INV board fault
Open-circuited IPM/Disconnected ACCT sensor
●ACCT sensor fault
●Broken compressor wiring
●Inverter circuit fault (IPM fault)
Incorrect wiring
●ACCT sensor fault
THHS sensor/circuit fault
●THHS sensor fault
(Thermistor fault, pinched lead wire, missing pins on
the connectors)
●Thermistor input circuit fault on the circuit board
●INV board fault
Serial communication error
●Communication error between control board and
INV board (noise interference, broken wiring)
IPM system error
●INV board switch setting error
●Wiring or connector connection failure between
connectors on IPM-driven power supply circuit
●INV board fault
-
(Preliminary : 4300)
Address overlap
●There are two or more of the same address.
6830
Non-consecutive address, system error
●Address setting error (Non-consecutive address)
7105
Remote controller signal reception error 1
●Remote controller cables are not connected.
●Broken wiring
●Broken remote controller wiring
●Communication circuit fault on the control board
6831
Remote controller signal transmission error
●Communication error due to external noise interference
●Communication circuit fault on the control board
6832
Remote controller over current
●
Remote controller cable is short
6833
Remote controller signal reception error 2
●Communication error due to external noise interference
●Communication circuit fault on the control board
●Broken or open 4-20mA signal output device wiring
(CN421)
6834
Address setting error
●Address setting error (Non-consecutive address)
7105
Incompatible combination of units
●
Different types of units are connected to the same system.
7130
No.-of-connected-unit setting is incorrect
●No.-of-connected-unit setting is incorrect (Main unit)
Analog input error
(Control board (MAIN) CN421)
●Analog input type fault
See item code 21
7102
4126
1001
Communication error between Main & Sub units
Communication error between the MAIN and SUB circuits
●Connector contact failure at CN102 on the control board
●Contact failure at the MA-MB terminal block on the
MAIN circuit or terminal block TB3 on the SUB circuit.
6500
Inverter fault
Remote controller error
(incl. remote controller
wiring fault)
Multiple unit
system error
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 118)
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 119)
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 120)
5110
(Preliminary : 1214)
(Details COMP : 01)
(Details FAN : 05)
0403
(Preliminary : 4300)
(Preliminary : 4305)
(Details COMP : 01)
(Details FAN : 05)
*Preliminary error codes will not appear on the 7-segment LED.
Error Type
Cause
(problem with the installation
environment/setting error)
Cause
(component problem)
Remote
SWS1
Operation SW
Error code
*1
(PCB
*2
RC M-NET)
Resetting the error
*3
Unit side
(PCB)
0000001906.book 128 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......