VII
Control ]
- 91 -
HWE15070
GB
Bypass Control
-5- Outdoor unit fan
The fan's rotation speed will be controlled to approximate the values in the table below that are obtained based on the outside
temperature and the low pressure.
(Pressures and temperatures will be monitored, and the fan frequency will change accordingly in three steps.)
Compressor Frequency Control
-6- Injection LEV
Operating range of the LEV
Opening range: 50-480 (fully open)
LEV operation speed
Open 133 plus/sec
Close 200 plus/sec
At startup
For one minute after startup, the valve will be fixed to Initial Setting 1.
Between one and five minutes after startup, the valve will be fixed to Initial Setting 2.
During operation
Five or more minutes after startup, LEV2 (Injection LEV) opening will be controlled every 30 seconds to approximate the dis-
charge SH to the target value according to the changes in high pressure and discharge gas temperature.
(Refer to the table below for the target discharge SH values.)
Fan rotation
speed (rpm)
Frequency (Hz)
Outdoor temp.(A)
(°C)
Fan rotation
speed (rpm)
Frequency
(Hz)
Outdoor temp.(A)
(°C)
270
31
37 < A
≤
40
450
50
12 < A
≤
17
300
34
32 < A
≤
37
490
55
7 < A
≤
12
330
37
27 < A
≤
32
550
60
2 < A
≤
7
370
41
22 < A
≤
27
600
66
0 < A
≤
2
410
45
17 < A
≤
22
670
73
A
≤
0
Target discharge SH (Item code c31: Discharge gas temp. - discharge pressure saturation temperature)
Refer to Chapter IX [1] 2. "Checking the sensor status." (page 115)
Outlet water temperature (B) (°C)
Outside temp.(A) (°C)
≤
-20
-20< A
≤
-17
-17< A
≤
-14
-14< A
≤
-11
-11< A
≤
-8
B
≤
45
20-35*
20-35*
20-35*
20-35*
35
45 < B
≤
50
20-30*
20-30*
20-30*
20-30*
30
50 < B
≤
55
20-25*
20-25*
20-25*
20-25*
25
55 < B
≤
60
20
20
20
20
20
60 < B
≤
65
20
20
20
20
20
65 < B
20
20
20
20
20
Outlet water temperature (B) (°C)
Outside temp.(A) (°C)
-8< A
≤
-5
-5< A
≤
-2
-2< A
≤
1
1< A
≤
5
5< A
B
≤
45
40
45
50
55
close
45 < B
≤
50
35
40
45
50
close
50 < B
≤
55
30
35
40
45
close
55 < B
≤
60
25
30
35
40
close
60 < B
≤
65
23
26
30
35
close
65 < B
20
23
27
32
close
*The target discharge SH will vary, depending on the operating frequency of the compressor.
0000001906.book 91 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......