(8) Setting the water temperature using analog signal input
Select the analog input format
• When dip switch SW2-7 is set to ON (Enable external input), the target water temperature varies with the preset
temperatures A and B and the type of analog input signal.
• When the water temperature setting input signal type is set to 0 (4-20 mA)
• External analog input signal of 5.9 mA: Preset temp. A (Item code 11)
• External analog input signal of 18.3 mA: Preset temp. B (Item code 13)
• External analog input signal of between 5.9 and 18.3 mA: the preset temperature will be linearly interpolated.
• When the water temperature setting input signal type is set to 1 (0-10 V)
• External analog input signal of 1.0 V: Preset temp. A (Item code 11)
• External analog input signal of 9.1 V: Preset temp. B (Item code 13)
• External analog input signal of between 1.0 and 9.1 V: the preset temperature will be linearly interpolated.
• When the water temperature setting input signal type is set to 2 (1-5 V)
• External analog input signal of 1.5 V: Preset temp. A (Item code 11)
• External analog input signal of 4.5 V: Preset temp. B (Item code 13)
• External analog input signal of between 1.5 and 4.5 V: the preset temperature will be linearly interpolated.
3
W
S
2
W
S
-10
5
6
7
8
9
10
Switch settings
OFF
OFF
OFF
OFF
OFF
ON
OFF
Items that can be set
Item
code
Initial
value
Unit
Setting
Note
Setting change from
an optional remote
controller
Incre-
ments
Lower
limit
Upper
limit
Select the analog input
format
1051
0
1
0
3
Not possible
Select "0"
0: Water temperature input 4-20 mA
1: Capacity control input 4-20 mA
2: Water temperature input IT terminal
3: Capacity control input IT terminal
Preset temp B
Preset temp A
5.9 mA
Input current
18.3 mA
Preset temperature = (B - A) * (Input current - 5.9 mA) / 12.4 mA + A
Change of 0.12 mA or less is not recognized.
Preset temp B
Preset temp A
1.0 V
Input voltage
9.1 V
Preset temperature = (B - A) * (Input voltage - 1.0 V) / 8.1 V + A
Change of 59 mV or less is not recognized.
Preset temp B
Preset temp A
1.5 V
Input voltage
4.5 V
Preset temperature = (B - A) * (Input voltage - 1.5 V) / 3.0 V + A
Change of 29 mV or less is not recognized.
0000001906.book 81 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......