VII
Control ]
- 101 -
HWE15070
GB
Operation Mode
-14- Controlling the operation of unit using external water temperature sensors
The water temperature can be controlled using the built-in sensor on the unit or a separately sold external water temperature
sensor.
The factory setting for the sensor option is "built-in sensor on the unit." (SW2-8: OFF)
To control the water temperature with an external water temperature sensor, set SW2-8 to ON.
(Note) If the settings for the dip switches are changed while the power to the circuit board is being supplied, reset the unit
according to the instructions in [6] (5) "Re-initializing the system" (page 24).
A separately sold water temperature sensor "TW-TH16" will be required to control the water temperature based on the exter-
nal water temperature reading.
It is possible to switch between two external water temperature sensors. Refer to the installation manual for how to set the
sensors.
Install the external water temperature sensor and wiring according to the instructions on the next page.
Operation Mode
-15- Remote water temperature setting input signal type
By setting SW2-7 to ON, external analog signals can be used to set the water temperatures.
Analog input type can be selected from the following four types:
"0": 4-20 mA
"1": 0-10 V
"2": 1-5 V
"3": 2-10 V
0000001906.book 101 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......