(10) Check for proper circulating water flow rate.
Measure the circulating water flow rate, if possible. If it is not, check that the temperature difference between the outlet and
inlet temperatures is between 3 and 5 ºC. A temperature difference of 6ºC or more indicates not enough water flow. Check
for air pockets in the pipe, and make sure that the pump has the appropriate capacity for the circuit.
(11) Check that the unit is operating properly according to the temperature adjustment function.
When a pull-down operation is completed, check that the hot water temperature adjustment function will come on and that the
unit will automatically go on and off. Make sure the ON/OFF cycle (beginning of an operation until the next) is at least 10 min-
utes. (The unit features an anti-short-cycling protection.)
Notes on temperature adjustment function
The water temperature can be controlled based on the inlet or the outlet temperature sensor reading. Select one to use. Refer
to "VII [1]1.Factory Switch Settings (Dip switch settings table)(page 67) and "(1)Setting procedures"(page 71) for how to select
the water temperature control method and how to set the water temperature.
(12) Connect the pump-interlock wire to the appropriate contacts.
1) Connecting the pump-interlock wire
Connect the pump-interlock wire to the pump-interlock circuit (Terminal block and ). The unit will not operate unless this
circuit is complete.
2) Notes on connecting the pump-interlock wire
Connect an NO relay (solenoid switch) for the pump.
This circuit is a low-voltage circuit. Keep the pump-interlock wire at least 5 cm away from any wire that carries a voltage of
100 V or above to avoid damage to the circuit board.
(13) Checking the rotation direction of the pump
Check that the circulating water pump is rotating in the correct direction. If the pump is rotating in the wrong direction,
disconnect the pump wiring from the solenoid switch, and reconnect them so that the pump will rotate in the correct direction.
Do not disconnect the power wire to the compressor in an attempt to keep the compressor from going into operation
during test run. (If it is done, the control board will not sense that the compressor is stopped, and the water temperature
will not be controlled properly and the unit may come to an abnormal stop.)
11
12
MP
51P
52P
52P
51P
71
3
1
70
PL pump fault
Recommended pump circuit
F
M
3
㨪
Control board on the unit
Control box on the unit
11
12
52P
0000001906.book 106 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......