VII
Control ]
- 86 -
HWE15070
GB
(11) Setting the booster heater 2 operation conditions
A temperature at which the booster heater 2 will go into operation (TWL) can be selected.
Select item code 1059 and 1060 to set the threshold temperature (TWL2 and TAL2) for booster heater operation.
Booster heater 2 operation conditions
•Individual system
The operation command signal is ON and at least one of the following two conditions is met.
The booster heater 2 signal of the MAIN circuit comes on.
•Multiple system
The operation command signal is ON and the following condition is met.
The booster heater 2 signal of the MAIN circuit comes on.
Booster heater 2 operation-stop conditions
The operation command signal is OFF or all of the following two conditions are met.
(*)Unit's inlet water temperature: Average value between the water temperature settings of the MAIN and SUB
circuits
Setting procedures
Set the dip switches on the circuit board as follows to change the settings.
1 Water-temperature control option is set to OFF, the water temperature drops below
TWL2, and the outside temperature drops below TAL2.
2 Water-temperature control option is set to ON, the external water temperature sensor
reading drops below TWL2, and the outside temperature drops below TAL2.
External water temperature sensor readings (TH14 and TH15) drop below TWL2, and
the reading of the outside temperature sensor connected to the MAIN circuit of the
main unit drops below TWL2.
1 The water temperature is at or above TWL2+2°C or the outside temperature is at or
above TAL2+2°C.
2 External water temperature sensor readings (TH14 and TH15) are at or above
TWL2+2°C, or the reading of the outside temperature sensor (TH9) connected to the
MAIN circuit of the main unit exceeds TAL2+2°C.
Step 1
Outdoor temperature
input source selection
3
W
S
2
W
S
-10
5
6
7
8
9
10
Switch settings
OFF
OFF
OFF
OFF
ON
OFF
OFF
Items that can be set
Item
code
Initial
value
Unit
Setting
Note
Setting change from
an optional remote
controller
Incre-
ments
Lower
limit
Upper
limit
Outdoor temperature
input source selection
1080
0
1
0
1
Not possible
0: Outdoor temperature sensor (TH9)
1: IT terminal
0000001906.book 86 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......