Read Before Servicing ]
- 8 -
HWE15070
GB
[6] Refrigerant Charging
1. Reasons
R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged
with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is charged frist
while the rest of refrigerants remain in the cylinder.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[7] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, all of the remaining refrigerant must be replaced with a new charge to maintain the proper composition
of the refrigerant. Repair the leak, and then charge the system with the specified amount of refrigerant (5.5 kg). (Charge refrigerant
in the liquid state.)
Refer to "IX [4] Refrigerant Leak."(page 146)
Cylinder with a siphon
Cylinder color R407C is Gray.
Refrigerant charging in the liquid state
Charge refrigerant through the
check joint on the high-pressure side.
Charging refrigerant through the
check joint on the low-pressure side
will create reverse pressure,
resulting in compressor malfunctions.
Cylin-
der
liquid
Valve
Valve
liquid
Cylin-
der
Cylinder without a siphon
0000001906.book 8 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......