VII
Control ]
- 93 -
HWE15070
GB
-9- Anti-short-cycling protection
The unit has a function to keep the compressor from short-cycling when the amount of circulating water is low or when the
load is light. After the compressor cycles off, it will not restart for 10 minutes.
The unit has a 3-minute restart-delay function to protect
the compressor from short-cycling. This function is effec-
tive even after a power failure.
Compressor
ON
OFF
Time
Min. 3 minutes
3-minute restart delay function
The 3-minite restart-delay function will
be triggered in the following situations:
(1) The setting for the SWS1 (Local,
Off, Remote) was changed, or (2) after
a power failure.
Min. 10 minutes
15 minutes
10 minutes
Compressor
ON
ON for
7 minutes
ON for
12 minutes
ON for
6 minutes
ON for
4 minutes
3 minutes
3 minutes
OFF
Time
0000001906.book 93 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......