VII
Control ]
- 73 -
HWE15070
GB
(2) Scheduled operation
Up to three sets of start/end times can be assigned for each day.
To operate the units according to the schedule, set the item code 5 to "1", and set the time for item codes 1, 6 through 9,
18 and 19.
Note
The operation schedule function will operate only when SWS1 is set to "REMOTE."
Setting procedures
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF setting is set to OFF.
Step 1
Set the dip switches
SW2 and SW3.
Set the dip switches on the circuit board as follows before making the settings for the items
described in this section.
Step 2
Select the desired
item with the push
switch SWP3.
Item codes 1, 5 through 9, 18, and 19 relate to scheduled operation setting.
Set the item code to 1, and set the time for each of the relevant items.
Press the push switch SWP3 to select an item code.
Use the push switches SWP1 and SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.
Step 3
Press the push
switches SWP1 (↑)
or SWP2 (↓) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
SW2
SW3
-10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
OFF
ON
OFF
Settings table
Settable item
Item
code
Initial
value
Unit
Limits and increments
Increments
Lower limit
Upper limit
9
5
3
2
0
0
0
0
e
t
u
n
i
m
1
e
t
u
n
i
m
:
r
u
o
H
0
0
0
0
1
e
m
i
t
t
n
e
r
r
u
C
Enable or disable scheduled
operation (ON/OFF)
5
0
Enable: 1
Disable: 0
1
0
1
Operation start time 1
6
0000
Hour: minute
1 minute
0000
2359
Operation end time 1
7
0000
Hour: minute
1 minute
0000
2359
Operation start time 2
8
0000
Hour: minute
1 minute
0000
2359
Operation end time 2
9
0000
Hour: minute
1 minute
0000
2359
Operation start time 3
18
0000
Hour: minute
1 minute
0000
2359
Operation end time 3
19
0000
Hour: minute
1 minute
0000
2359
Note
A mode (preset temperatures) can be selected for each operation time period. See the next page
for how to make the settings.
Note
If Code 5 is set to "1," lock the remote controller's schedule function.
Step 5
Press the push
switch SWP3 to
save the change.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
0000001906.book 73 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......