VII
Control ]
- 74 -
HWE15070
GB
[When the operation Start/End times do not overlap]
If "Start time1 - End time 1", "Start time 2 - End time 2", "Start time 3 - End time 3" overlap, the settings for the period with a larger
number will be ineffective.
[When operation period 1 and 2 overlap]
If two or more operation periods overlap, the settings for the period with a larger number will be ineffective.
If Start time 1 and start time 3 are set to the same value, the setting for Start time 3 will be ineffective.
Set the setting for Start time 3 to a time at least one minute after End time 1.
(Once the compressor stops when End time 1 comes, the 3-minute restart delay function will keep the compressor from restarting for
three minutes. Because of this, even if Start 3 time is set to a time within three minutes after End time 1, the compressor will not start
right away.)
[When operation periods 1 and 3 overlap]
[When operation periods 2 and 3 overlap]
[When operation periods 2 and 3 overlap]
(*) Refer to the section on how to select the preset water temperatures on the next page.
Operation Period 1
Operation Period 2
Operation Period 3
Target water temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 1
Operation Period 2
Operation Period 3
Set temp.
Operation command
signal
Operation Period 2
Item code 1219 setting
ON
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
Item code 1218 setting
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1220 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
Item code 1219 setting
ON
Operation Period 1
ON
Operation Period 2
Item code 1218 setting
Operation Period 3
ON
Operation Period 1
0000001906.book 74 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......