VII
Control ]
- 85 -
HWE15070
GB
Select item code 1057 and 1058 to set the operation temperature (TWL1 and TAL1) for the booster heater 1.
Press push switch SWP3 to select the item code.
Change the values with push switches SWP1 and SWP2.
Until the changed values are saved, the values will blink.
Press and hold push switches SWP1 and SWP2 to fast forward the numbers.
Press SWP3 once within one minute of changing the settings to save the change.
When the new setting is saved, the display will stop blinking and stay lit. The display will, then, return to the item code
display mode.
If SWP3 is not pressed within one minute, the change will not be saved, and the display will return to the item code
display mode.
Step 2
Set dip switches
SW2 and SW3.
3
W
S
2
W
S
-10
5
6
7
8
9
10
Switch settings
OFF
OFF
OFF
OFF
OFF
ON
OFF
Step 3
Select the item to be set with
push switch SWP3.
Step 4
Change the values with push
switches SWP1 (↑) or SWP2 (↓).
Items that can be set
Item
code
Initial
value
Unit
Setting
Note
Setting change from
an optional remote
controller
Increm-
ents
Lower
limit
Upper
limit
Booster heater 1
operation water
temperature (TWL1)
1057
40
°C
0.1
0
70
Not possible
Booster heater 1
operation outside
temperature (TAL1)
1058
-10
0.1
-30
50
Step 5
Press push switch SWP3 to save
the changed value.
0000001906.book 85 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......