IX
Troubleshooting ]
- 139 -
HWE15070
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the
INV board er-
ror detection
circuit.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Overcurrent error
(4250 Detail code No. 101, 104,
105, 106, and 107)
Replace the INV board.
(2)
Put the outdoor unit
into operation.
2)
Logic error
(4220 Detail code No. 111)
Replace the INV board.
3)
ACCT sensor circuit failure
(5301 Detail code No.117)
Replace the INV board.
4)
IPM open
(5301 Detail code No.119)
Normal
[2]
Check for
compressor
ground fault
or coil error.
Disconnect the compressor
wiring, and check the com-
pressor Meg, and coil resis-
tance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
Check that there is no liquid re-
frigerant in the compressor.
If there is none, replace the com-
pressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.092 ohm
(20°C)
Replace the compressor.
[3]
Check wheth-
er the inverter
is damaged.
(No load)
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Inverter-related problems are de-
tected.
Connect the short-circuit connec-
tor to CN6, and go to section [1].
(2)
Disconnect the short-
circuit connector from
CN6 on the INV
board.
2)
Inverter voltage is not output at the
terminals (SC-U, SC-V, and SC-W)
Replace the INV board.
(3)
Put the outdoor unit
into operation.
Check the inverter
output voltage after
the inverter output
frequency has stabi-
lized.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
4)
There is no voltage imbalance be-
tween the wires.
Normal
*Reconnect the short-circuit con-
nector to CN6 after checking the
voltage.
0000001906.book 139 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......