IX
Troubleshooting ]
- 125 -
HWE15070
GB
*Preliminary error codes will not appear on the 7-segment LED.
Error Type
Cause
(problem with the installation
environment/setting error)
Cause
(component problem)
Remote
SWS1
Operation SW
Power supply fault
Active filter fault
Heat exchanger freeze up
Discharge temperature fault
*8
*7
4106
(Details : 255)
4121
(Preliminary : 4171)
AC61
(Preliminary AC71)
1104
Current-related problem
during normal operation
IPM error
4250
4255
(Preliminary : 4350)
(Preliminary : 4355)
(Details :
101)
4250
4255
(Preliminary : 4350)
(Preliminary : 4355)
(Details :
102)
4250
4255
(Preliminary : 4350)
(Preliminary : 4355)
(Details :
103)
4250
4255
(Preliminary : 4350)
(Preliminary : 4355)
(Details :
107)
●After a power reset, if nomal power suppy is not detected five consecutive times at 20
ms intervals,this will be regarded as an error.
●A suction temperature of -2ºC or below has been detected for 10 seconds during the
defrost cycle and 30 seconds after the initiation of the defrost cycle.
●Incorrect dip switch setting
●Incorrect SW2-4 setting
●Transmission power supply output fault
Wiring fault
Detection of overcurrent in the transmission power supply
●Transmission power supply power reception fault
In a multiple unit system, one unit started supplying power,
but the other units have not.
Transmission power supply fault
Transmission voltage detection circuit fault
●4-way valve switching failure
●High-pressure sensor fault
●Discharge refrigerant thermistor fault
●Linear expansion valve fault (Main circuit LEV, injection LEV)
●Injection solenoid valve fault
●Fan motor error
●Fan inverter fault
●Refrigerant shortage (gas leakage)
●Thermistor input circuit fault on the control board
●INV board fault
●Ground fault of the compressor or fan motor
●Coil fault on the compressor or fan motor
●IPM fault (loose terminal screws, cracks due to swelling)
●Items in the "Heatsink overheat protection" row in the
"Cause" column.
●INV board fault
●Compressor ground fault
●Coil failure
●IPM fault (loose terminal screws, cracks due to swelling)
●Water depletion
●Abrupt water temperature change
(5K/min or greater)
●Pump fault
●Drop in water flow or water outage
during defrost
●
Water temperature drop during defrost
●30 seconds after the compressor has
started up
●An overcurrent was detected by the
overcurrent detection resistor (RSH) on
the INV board.
●An IPM error signal was detected.
ACCT overcurrent
●30 seconds after the compressor has
started up
●A peak current of at or above 56A or 33
Arms was detected by the current sensor.
DCCT overcurrent
●30 seconds after the compressor has
started up
●A peak current of at or above 56A or 33
Arms was detected by the current sensor.
Overcurrent relay trip (effective value)
(During normal operation)
●30 seconds after the compressor has
started up
●A current of at or adove 33 Arms was
detected by the current sensor.
●Preliminary : A discharge temperature of 120ºC or above has been detected for 30
seconds while the compressor is in operation.
●Error : The above preliminary error was detected three times.
●Error : A discharge temperature of 125ºC or above was detected momentarily.
Inverter fault
Error code
*1
(PCB
*2
RC M-NET)
Resetting the error
*3
Unit side
(PCB)
0000001906.book 125 ページ 2015年11月5日 木曜日 午前11時55分
Summary of Contents for CAHV-P500YB-HPB
Page 1: ......
Page 7: ...CONTENTS HWE15070 GB ...
Page 9: ... 2 HWE15070 GB ...
Page 19: ... 12 HWE15070 GB ...
Page 37: ... 30 II Restrictions GB HWE15070 ...
Page 39: ... 32 HWE15070 GB ...
Page 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Page 49: ... 42 HWE15070 GB ...
Page 57: ... IV Remote Controller 50 HWE15070 GB ...
Page 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Page 59: ... 52 HWE15070 GB ...
Page 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Page 67: ... 60 HWE15070 GB ...
Page 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Page 73: ... 66 HWE15070 GB ...
Page 111: ... 104 HWE15070 GB ...
Page 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Page 119: ... 112 HWE15070 GB ...
Page 163: ... IX Troubleshooting 156 HWE15070 GB ...
Page 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Page 165: ... 158 HWE15070 GB ...
Page 167: ... X Attachments 160 HWE15070 GB ...
Page 168: ......