User Switches C1 Submenu
86
Parameter
[Alphanumeric]
Description
Choices
Default
Hidden
item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Brake Hold
Src
[C127]
(Brake Hold Source)
If set to internal, the drive will command
the mechanical brake to hold mode until
confirmation of brake picked exists.
internal
[1]
serial
[2]
INTERNAL
Y
Y
Brk Pick Flt
Ena
[C128]
(Brake Pick Fault Enable)
When this parameter is set to ENABLE,
the brake pick command and confirmation
must match within the specified time in
BRK PICK TIME (A1) parameter or a
brake pick fault is declared.
enable
[1]
disable
[0]
active
[2]
DISABLE
Y
Y
Brk Hold Flt
Ena
[C129]
(Brake Hold Fault Enable)
When this parameter is set to ENABLE,
the brake hold command and confirmation
must match within the specified time in
BRK HOLD TIME (A1) parameter or a
brake hold fault is declared.
enable
[1]
disable
[0]
DISABLE
Y
Y
Ext Torq
Cmd Src
i,ii
[C130]
(Torque Command Source
i
,ii
)
Sets the source of the external torque
command when the SPEED REG TYPE
(C1) is set to external reg. NOTE:
if SPEED REG TYPE is set to external
reg and EXT TORQ CMD SRC is set to
serial, the drive is a torque controller
if SPEED REG TYPE is set for a speed
regulator (either pi speed reg or elev spd
reg) and EXT TORQ CMD SRC is set to
either serial, the torque command is an
auxiliary torque command (torque
feedforward command)
none
i
,ii
[0]
serial
i
,ii
[1]
analog input
i
,ii
[2]
NONE
i,ii
Y
i
,ii
Y
i
,ii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation