Comfort System

Installation Instructions for Z-300-HC Zone Control Panel

Heat / Cool Auto Changeover - Cooling Priority

Installation Notes:

Connect only 24 Vac to Control
Panel.

Zone dampers are powered
closed / spring return open.

Specifications:

Terminal Designations:

To install the panel, first slide the PC
board out of its base and screw the
base to a flat surface next to the
HVAC equipment. The PC board
should be reinstalled by centering it
over the base and pushing firmly.

The control panel requires a
separate 24 Volt transformer.

No special wire is required.

The thermostat and motorized
dampers may be located up to 300
feet from the control panel when
using 18 gauge thermostat wire.

The left fuse (4 Amp) protects the
relay contacts. The right fuse (4
Amp) protects the printed circuit
board.

If condensing unit is not equipped
with short cycle protection timer,
(TD-5) should be installed.

The two wires from the condensing

unit should be connected to the ‘Y’
and transformer common terminals
at the furnace.

The low limit (FS-38) should be
wired to the ‘LL’ terminals on the
panel (remove jumper). The
compressor will shut off when low
limit trips out.

The high limit (HL-170) should be
wired to the ‘HL’ terminals on the
panel (remove jumper). The furnace
will shut off when high limit trips out.

A 40 VA transformer will power the
panel and up to four (4) dampers.
A 75 VA transformer will power the
panel and up to seven (7) dampers.

Up to three (3) dampers can be
connected in parallel. A total of no
more than seven (7) dampers may
be connected to the system. A
system may be a single panel or
multiple panels.

If more than three (3) zones are
required, two additional panels can
be used to control up to a total of
nine (9) zones. T5 terminal strip is
used only when more than three
zones are required.

Label the dampers, damper wires
and thermostat wires with the zone
number and the area they serve.

Panel Dimensions:
Height:

5.0 inches

Width:

10.0 inches

Depth:

2.0 inches

Mounting:
2 back plate screws

Operating Ambient Temperature:
-20° to 160° F

Power Supply:
24 Vac 40VA / 75 VA transformer

W =

Heat

Y =

Cool

G =

Fan

R =

Hot 24 Volt

X =

Common

D =

Damper

LL =

Freeze Stat

HL =

High Limit

H =

Hot 24 Volt

X =

Ground or Common

ZONE 1

ZONE 2

ZONE 3

CONT

ACTS

4

AMP

FUSES

PC

BOARD

COOLING
PRIORITY

POWER

HEAT

COOL

FAN

ZONE 1

CALLING

ZONE 2

CALLING

ZONE 3

CALLING

HVAC UNIT

W Y G

R X D D

W Y G

R X D D

W Y G

R X D D

4

AMP

W Y G

R

H X

LL LL HL HL

T5

Comfort System™

Z-300-HC

PATENTED 5,944,098

4

AMP

W Y G

R C

W Y G

R C

D

SINGLE STAGE

HEAT / COOL

THERMOSTAT

DAMPER MOTOR
0.36 AMPS 10 VA

HVAC UNIT

TERMINAL

STRIP

LOW

LIMIT

HIGH
LIMIT

120/24 VAC

TRANSFORMER

H X

W Y G R

LL LL

HL HL

D

D

W Y G

R X

WIRE THE SAME

AS ZONE 1

FAN LED INDICATES

WHEN A

THERMOSTAT IS

CALLING FOR FAN.

WHEN GREEN ZONE

LEDS ARE ON, THOSE

ZONES ARE CALLING

FOR HEATING OR COOLING

1

2

3

4

5

6

JUMPERS

TM