Alarm mode
The condition monitor enters alarm mode when either vibration or temperature limits are exceeded over
two consecutive readings within a ten minute period. Alarm mode is indicated with two red flashing LEDs
within two second intervals.
Temperature and vibration limits
Variable
Limit
Temperature 91°C | 195°F
Vibration
100% increase over the baseline level
Battery life
The i-ALERT
®
2 Condition Monitor battery is not replaceable.
You must replace the entire unit once
the battery runs out of power.
The battery life is not covered as part of the standard pump warranty.
This table shows the average condition monitor battery life under normal and alarm-mode operating condi-
tions.
Condition monitor operational state
Battery life
Normal operating and environmental conditions Three to five years
Alarm mode
One year
3.3 Nameplate information
Important information for ordering
Every pump has nameplates that provide information about the pump. The nameplates are located on
the casing and the bearing frame.
When you order spare parts, identify this pump information:
•
Model
•
Size
•
Serial number
•
Item numbers of the required parts
Item numbers can be found in the spare parts list.
Refer to the nameplate on the pump casing for most of the information. See Parts List for item numbers.
Nameplate types
Nameplate
Description
Pump casing
Pump
Provides information about the hydraulic characteristics of the pump.
The formula for the pump size is: Discharge x Suction - Nominal Maximum Impeller Diameter in
inches.
(Example: 2x3-8)
Bearing frame
Provides information about the lubrication system used.
ATEX
If applicable, your pump unit might have an ATEX nameplate affixed to the pump, the base-
plate, or the discharge head. The nameplate provides information about the ATEX specifica-
tions of this pump.
3.3 Nameplate information
Model CV 3196 i-FRAME Installation, Operation, and Maintenance Manual