6. Troubleshooting and check
6-5
[Servo drive overload characteristics curve]
(note1) If Ano-03 (OVER LOAD) happens often, refer servo drive overload characteristic-
curve and re-establish suitable load of servo motor.
(note2) The overload alarm occurs 25% faster when the motor is in the Stall state.
6.2. Precautions
- When measuring motor voltage: The voltage output from the servo amplifier to the motor is
PWM controlled, so the waveform of pulse phase is output. Since the indicated value can
vary greatly depending on the type of instrument, be sure to use a rectified voltmeter for
accurate measurements.
- When measuring the motor current: The pulse waveform is smoothed to a certain sine wave
by the reactance of the motor, so connect the moving iron type ammeter directly.
Rated
current
(%)
Overload operation
time
Min.
Max.
Set
value
100
∞
120
∞
150
300
1500
760
200
60
150
107
250
20
40
30
300
6
15
7
100
10
10000
1000
100
Motor rated current (%)
300
250
200
150
O
p
e
ra
tin
g
t
im
e
(se
c)
Summary of Contents for FDA7000 Series
Page 42: ...1 Model check and handling 1 35...
Page 57: ...2 Wiring and connection 2 14 Drawing C Order Code Please contact our sales office...
Page 130: ...3 Parameter setting 3 51...
Page 167: ...5 Servo operating 5 10...
Page 188: ...8 External view 8 2 External view B CN1 CN3 CN2 External view C...
Page 189: ...8 External view 8 3 External view D External view E...
Page 190: ...8 External view 8 4 External view F External view G...
Page 192: ...8 External view 8 6 External view I External view J...
Page 193: ...8 External view 8 7 External view K External view L...
Page 194: ...8 External view 8 8 External view M...
Page 195: ...8 External view 8 9...