A-2 Regenerative resistor
A-8
A
ppendi
x
Apx
Examination of regenerative energy
Examine installing a regenerative resistor in the following conditions:
Drive with high inertia moment and load.
The system is stopped frequently.
Continuous regeneration occurs such as when the load moves up and down
In these cases, calculate the regenerative energy and check the power that can be absorbed by
the built-in regenerative resistor of the driver. If the regenerative energy is greater, install an
external regenerative resistor.