11-1 Alarms and remedial actions
11-10
2
3
4
5
6
7
8
9
10
11
Appe
Troubl
esh
oot
ing
Alarm
code
Alarm name
Description
Condition at
occurrence
Action
AL60
Excessive
deviation
The deviation
counter value
exceeded the
pulse count set
in [SP49:
Allowable
position
deviation].
The alarm
occurs during
acceleration or
deceleration:
Excessive command pulse frequency
→ Lower the command output pulse frequency
on the host device. The frequency should
not exceed the actuator’s rated rotation
speed (r/min) multiplied by 60.
Excessive load inertia moment
→ Lower the load inertia moment.
→ Slowly increase/decrease the command
pulse frequency on the host device.
The speed
does not rise
with the
command, and
the alarm
occurs
sometime after
that:
Cause: The input signal FWD inhibit or REV
inhibit is enabled.
The signal logic is set to normally closed for
[SP03: FWD inhibit input setting] and
[SP04: REV inhibit input setting], but the
signals are not assigned to CN2.
→ Assign the signals to CN2 and wire them
according to the normally closed logic.
The respective signals are assigned to CN2
and their logic is set to normally closed for
[SP03: FWD inhibit input setting] and
[SP04: REV inhibit input setting], but the
assigned pins are open.
→ Wire the signals according to the normally
closed logic.
The respective signals are assigned to CN2
and their logic is set to normally open for
[SP03: FWD inhibit input setting] and
[SP04: REV inhibit input setting], but the
assigned pins are closed.
→ Wire the signals according to the normally
open logic.
Large friction torque and load torque
→ Confirm that holding brake is released.
→ Confirm that the actuator output torque is
sufficient to handle load torque.
The actuator
does not
rotate and the
alarm occurs:
Poor motor cable connection or wrong
phase order
→ Connect the motor cable wires and
terminals securely.
→ Connect the motor wires and terminals in
the correct phase order.
Poor connection of the encoder connector
(CN1)
→ Securely connect the encoder connector
again.
Large friction torque and load torque
→ Confirm that holding brake is released.
→ Confirm that the actuator output torque is
sufficient to handle load torque.
Summary of Contents for H A - 800A
Page 60: ...2 6 Wiring the host device 2 21 4 2 2 1 9 8 7 6 9 8 Installation wiring...
Page 86: ...3 6 Normal operation 3 25 4 3 3 1 9 8 7 6 9 8 Startup...
Page 152: ...5 8 Connection example in control mode 5 35 1 2 3 4 5 6 7 8 9 10 11 Appe I O signals...
Page 166: ...6 1 Operating display panel 6 13 11 10 9 4 7 6 5 4 3 2 1 Panel display and operation...
Page 206: ...8 2 Function extension parameter 8 17 1 2 3 4 5 6 7 8 9 10 11 Appe System parameter mode...
Page 222: ...9 2 Details of test mode 9 15 1 2 3 4 5 6 7 8 9 Test mode...
Page 270: ...11 2 Warnings and remedial actions 11 17 1 2 3 4 5 6 7 8 9 10 11 Appe Troubleshooting...
Page 271: ...1 16 Chapter 12 Option Options you can purchase as necessary are explained 12 1 Option 12 1...
Page 276: ...12 1 Option 12 5 1 2 3 4 5 6 7 8 12 Option...