MAN3186 - TITANUS MICRO
•
SENS®
187
7.6 Function test
If the TITANUS MICRO·SENS® cannot be calibrated, check its functionality
using the test pipe, digital fine pressure gauge with adapter, service PC and
diagnostic software.
The following describes the complete function test with digital fine pressure
gauge type GDH 01 AN. A limited function test is also possible without a
digital fine pressure gauge.
7.6.1 Preparing for the function test
► Make sure that the TITANUS MICRO·SENS® is in operation for at least
30 min.
► Disconnect the pipe system from the TITANUS MICRO·SENS®. After
expiration of the adjusted air flow fault delay time, the device should
report a fault. If no air flow fault is detected, the device is defective.
► Connect the test pipe.