MAN3186 - TITANUS MICRO
•
SENS®
61
DM-MB-TMx-x-10 [% light
obscuration/m]
0.1
… 2.0
DM-MB-TMx-x-50 [% light
obscuration/m]
0.5
… 2.0
4.2.2 Remote displays
Voltage
Current
All current consumptions specified refer to an ambient temperature of 20 °C.
Standby mode [mA]
15
Max. state [mA]
50
Electrical connection lengths [m]
Max. 1000
Dimensions
Weight
Protection class
Impact resistance
Housing
Temperature range
Displays on the device
Connections
1)
optional
Supply voltage (Ue) [V]
15
… 30
Nominal supply voltage [V DC]
24
H x W x D [mm]
70 x 140 x 200
[kg]
0.6
IP code in accordance with IEC/EN
60529
IP54
In accordance with IEC/EN 62262, EN
50102
IK 04
Material
Plastic (ABS)
Colour
RAL 9018, Papyrus white
[°C]
-
20 … +60
Deep freeze version [°C]
-
40 … +60
Operation
Green LED
Alarm
Red LED
Pre-alarm
1)
Red LED
Collective fault
Yellow LED
Bar graph
1)
Smoke level 1
… 10 (10x yellow LED)
Alarm location display
1)
5x red LED
Terminal connections [mm²]
0.5
… 2.5
Fire alarm cable
shielded (e.g. type J-Y(ST)Y)
Cable glands
8x M20, 6x M25