MAN3186 - TITANUS MICRO
•
SENS®
91
d
TITANUS MICRO·SENS®
5.3.2.1 I-pipe system
Image 51:
I-pipe system, e.g. equipment monitoring
Limit values
Min. distance between device to first aspiration aperture
2 m
Max. distance between device to first aspiration aperture
20 m
Max. overall pipe length of pipe Ø 25 mm
40 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
30 m
Min. distance between two aspiration apertures (d)
0.1 m
Min. distance between two aspiration apertures (d) for localising the
fire site
3 m
Max. distance between two aspiration apertures (d)
4 m
Max. number of aspiration apertures (n)
5 units
Table 34:
Limit values of I-pipe for simplified pipe project planning
Number of aspiration
apertures
1
2
3
4
5
Ø aspiration aperture [mm]
1)
6.8
4.6
4.0
3.6
3.4
Table 35:
Diameter of the aspiration apertures for the I-pipe system with simplified
project planning
1)
Punching diameter of the aspiration
‑
reducing film sheet