MAN3186 - TITANUS MICRO
•
SENS®
208
► Move the lever of the ball valve to the 90° setting.
► Make sure that the TITANUS MICRO·SENS® is disconnected from the
pipe system and the compressed air supply.
► Wait approx. 20 seconds. The dust and dirt stirred up in the pipe system
settles and thus cannot be drawn in via the TITANUS MICRO·SENS®.
► Move the lever of the ball valve to the 0° setting within 10 s.
► Make sure that the purged pipe system is connected to the
TITANUS MICRO·SENS® again.
8.5 Replacing the detection unit
Image 140:
Replacing the detection unit
► Unfasten the four cover screws of the detection unit using a screwdriver.
► Lift the detection unit out of the device base.
► Reconnect jumper X4 (pin 1,2 or 2,3) on the new detection unit.
► Determine the type of calibration against the test record.
► Insert the new detection unit into the device base. Pay attention to the
mechanical coding, which prevents the unit from being twisted.