MAN3186 - TITANUS MICRO
•
SENS®
119
6.4.1 Connecting to an FDCP, with reset button
Example
Device 1
Device n
Reset button
Principle of alarm connection
Indicator bus
1)
Line termination or output to the next device
Resistors are dependent on the connected FDCP.
Image 74:
Connecting to an FDCP, with reset button
6.5 Inserting and connecting the reset circuit
board
The reset circuit board can be optionally used in the
TITANUS MICRO·SENS®.
An additional housing is required for the installation of the reset circuit board.
It must be installed right next to the TITANUS MICRO·SENS®. If several
TITANUS MICRO·SENS® are connected to a detector line, a reset circuit
board is only connected to the detector line after the last device.
The reset circuit board can only be used if the standby current of the
detector line is between 5 mA and 50 mA and the termination resistor is
formed by an ohmic resistance. The reset impulse is triggered if the detector
line voltage falls below 3 V within 0.5 s when the FDCP is reset.