MAN3186 - TITANUS MICRO
•
SENS®
146
Detach aspiration-reducing film sheets
Should aspiration-reducing film sheets become partially or completely
detached from the aspiration pipe, detection in accordance with the project
specifications cannot be guaranteed.
► Avoid any contact with the adhesive surfaces to keep these free from
dust and grease.
NOTE
► Clean the drilling area along the entire pipe circumference to remove
any dirt and grease using Tangit cleaner.
► Select the size of the aspiration-reducing film sheet according to the
project planning guidelines.
► Adhere the aspiration-reducing film sheet to the centre of the drill hole.
► Secure the aspiration-reducing film sheet against detachment, if
necessary. Adhere the sleeve over the centre of the aspiration-reducing
film sheet. The diameter of the opening in the aspiration-reducing film
sheet must not be changed.
Risk of injury due to flammable liquids and vapours
Formation of explosive/highly flammable vapour/air mixtures is possible.
Injuries to health due to direct or indirect contact.
► Prior to processing, observe the safety notes of the manufacturer.
WARNING