MAN3186 - TITANUS MICRO
•
SENS®
11
2 Product description
You will find the characteristics and application areas in this chapter.
2.1 Characteristics
The TITANUS MICRO·SENS® belongs to the group of tried and tested
aspirating smoke detectors of WAGNER Group GmbH.
In addition to monitoring rooms and equipment, the
TITANUS MICRO·SENS® can be used to monitor air conditioning units or
ducts. Using the innovative ROOM IDENT method (optional), the unit can
also determine the location of the fire.
Fire site localisation (optional)
The unique ROOM IDENT technology enables the exact localisation of the
fire and monitoring of up to five separate areas. For the fastest possible
intervention of emergency services, the fire site can be marked, e.g. via
response indicators assigned to the different monitoring areas. By means of
a connected relay module, the localised fire site can be forwarded to a
superior fire detection control panel (FDCP).
Sensitivity
The TITANUS MICRO·SENS® has a response sensitivity (main alarm) of up
to 0.1 or 0.5 % light obscuration/m. By means of smoke level indication, a
display sensitivity of 0.01 to 0.05 % light obscuration/m is achieved. A wide
detection range across all standard types of blaze is achieved thanks to the
High Power Light Source technology. The unit can optionally have two
response sensitivities (pre-alarm and main alarm).
LOGIC·SENS
The intelligent signal processor LOGIC·SENS distinguishes between
deception variable and fire event to prevent false alarms.
PIPE·GUARD
In the same way as point-type smoke detectors, which are electronically
monitored for cable breaks and short-circuiting, highly sensitive and
operationally reliable air flow monitoring is required for aspirating smoke
detectors. The unique air flow sensor system used in all
WAGNER Group GmbH aspirating smoke detectors reliably detects
fluctuations in the air flow, for example due to breakage or the blockage of
the pipe system.
Air flow monitoring is temperature-compensated and can be set in relation to
air pressure.
Summary of Contents for Ampac TITANUS MICRO-SENS