66
5.1.2 Pipe system
When planning the pipe system, it must be ensured that reliable fire
detection is guaranteed for any fire present in an installation or in a
monitored area.
The number of aspiration apertures and the design of the pipe system
depend on the size and geometry of the monitoring area. The aspiration
apertures are to be planned like point detectors. The pipe system is to be
fitted in accordance with the project planning guidelines of this chapter while
taking the following points into consideration.
Pipe configurations
4 types of pipe layouts can be selected, depending on the room geometry:
Pipe configuration
Characteristic
I-pipe
Pipe system without branching
U-pipe
Pipe system that separates into
two branches after connection to the TITANUS MICRO·SENS®
M-pipe
Pipe system that separates into
three branches after connection to the TITANUS MICRO·SENS®
Double U-pipe
Pipe system that separates into
four branches after connection to the TITANUS MICRO·SENS®
Table 7:
Pipe configuration characteristics
To localise the fire site, I-pipe configuration must be planned.