MAN3186 - TITANUS MICRO
•
SENS®
180
No standard conformity in case of improper project planning
The function "Main alarm after ROOM IDENT" is not AS ISO 7240-
20 compliant.
NOTE
7.2.10 Activating or deactivating main alarm after
ROOM·IDENT (optional)
For certain applications, it may be useful to trigger the alarm only after
localising the fire site. If this function is to be activated, the "ROOM IDENT"
function must also be activated (see chapter "Activating or deactivating
ROOM IDENT (optional)"). Otherwise, there is no localisation of the fire site.
Detection unit
Main alarm after
ROOM·IDENT activated
Default setting
DM
‑
TMx
‑
xx
‑
10
‑
x
off - on
off
DM
‑
TMx
‑
xx
‑
50
‑
x
off - on
off
Table 60:
Main alarm after ROOM·IDENT
7.2.11 Setting the height above sea level
The altitude value corresponds to the height of the
TITANUS MICRO·SENS® installation site above sea level. The value must
be changed if the air flow sensors of the TITANUS MICRO·SENS® have to
be adjusted to air pressure. If the height above sea level is changed, the air
flow of the TITANUS MICRO·SENS® is automatically initialised again.
7.2.12 Setting the current air pressure
The current air pressure in the monitoring area must be entered if an air-
pressure-dependent adjustment is required. The default setting corresponds
to the mean air pressure at sea level. If the air pressure is changed, the
TITANUS MICRO·SENS® automatically performs an air flow initialisation.