MAN3186 - TITANUS MICRO
•
SENS®
33
Image 17:
Front film sheet of the detector box
Item
Components
Description
1
Infrared interface
Commissioning and fault diagnostics
2
Smoke level display
(1)
(bargraph, 10x yellow LED)
Current smoke level
(2)
3
Operation (green LED)
Operating indicator
4
Main alarm (red LED)
100% smoke level
5
Pre-alarm (red LED)
(1)
66% smoke level
6
Fault (yellow LED)
Pipe system fault, detector module fault or
failure of the fan
(1)
optional
(2)
As a result of signal fluctuation with regard to the smoke level in the
transmission range between two smoke level LEDs, the top active smoke
level LED can flicker.