MAN3186 - TITANUS MICRO
•
SENS®
89
d
TITANUS MICRO·SENS®
A
B
5.3.1.4 Double U-pipe system
Image 50:
Double U-pipe system for room monitoring
Limit values
Min. distance between device and T-piece
2 m
Max. distance between device and T-piece
20 m
Max. branch lengths
12.5 m
Max. overall pipe length of pipe Ø 25 mm
50 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
40 m
Min. distance between two aspiration apertures (d)
4 m
Max. distance between two aspiration apertures (d)
10 m
Max. number of aspiration apertures (n)
8 units
Table 31:
Limit values of double U-pipe system for single hole monitoring
Number of aspiration apertures
4
8
Ø aspiration aperture [mm]
1)
A
4.4
3.0
B
-
3.2
Table 32:
Diameter of the aspiration apertures of the double U-pipe system for single
hole monitoring
1)
Punching diameter of the aspiration
‑
reducing film sheet