MAN3186 - TITANUS MICRO
•
SENS®
12
In addition, a dynamic air flow sensor system can be activated in the
diagnostic software. This sensitises the device to quick changes in the air
flow, e.g. in the event the aspiration apertures are suddenly covered. An air
flow fault is already triggered at an air flow deviation of approx. 5%.
Plug
‑
and
‑
play
The plug-and-play function enables the TITANUS MICRO·SENS® to be
easily installed and commissioned.
The device base is pre-assembled on-site. Due to the presetting of the
detection unit for the standard application, the TITANUS MICRO·SENS® is
immediately ready for operation after installation in the device base.
Redundant fan (optional)
For the highest safety requirements, the TITANUS MICRO·SENS® can be
equipped with a redundant fan. ROOM IDENT is not possible when
operating the unit with a redundant fan.
Network capability (optional)
Several TITANUS MICRO·SENS® devices can be linked together in an
Ethernet network using a network module. The operator can monitor the
entire system including the smoke level, air flow values, etc. from a central
location using Visu
LAN
T
®
, for example. An integrated data logger allows the
data to be stored on a memory card over a longer period of time and
analysed later on. The TITANUS MICRO·SENS® can also be integrated into
existing danger and building management systems via what is referred to as
an OPC server.
Potential-free contacts
The TITANUS MICRO·SENS® has one potential-free contact each for alarm
and fault. This means that the unit can be switched to collective and
addressable detection lines of an FDCP (using the suitable addressing
modules).
A relay module (optional) can be connected to the
TITANUS MICRO·SENS®. With this, potential-free contacts are available for
alarm, fault and pre-alarm (RU-2) as well as for ROOM IDENT (RU-1).
Diagnostics
The diagnosis device is a system which provides quick and easy device
configuration and fault localisation for set-up operations, inspections and
servicing. Events are stored in the TITANUS MICRO·SENS® for 72 hours
for diagnosis purposes. The events are stored until they are manually
deleted using the diagnostic software.
Point-type detector project
planning
The aspiration apertures of the pipe system are equivalent to point-shaped
smoke detectors. The monitoring areas can therefore be planned in
accordance with the currently valid national directives.