Device damage due to application of compressed air
During start-up and purging, compressed air is applied that can result in
damage to the air flow sensor.
► Preferably use a 3-way ball valve.
► Disconnect the TITANUS MICRO·SENS® from the pipe system prior to
purging.
NOTE
8.4 Pipe system check
► Check the aspiration apertures of the pipe system for blockage in
monitoring areas where dust particles or icing are possible.
If the aspiration apertures are blocked, the pipe system must be purged (see
chapter "Purging the pipe system").
8.4.1 Purging the pipe system
A ball valve is required to purge the pipe system with compressed air or to
close off the pipe system and simulate a blocked pipe.
A single purging process must be fully completed within 50 s. If another
purging process is required, the above procedure is to be repeated after
120 s at the earliest.