MAN3186 - TITANUS MICRO
•
SENS®
205
1
2
3
4
3
5
scheme
position
position
position
0°
90°
180°
8.4.1.1 3
‑
way ball valve (ABS/PVC)
Image 138:
Installing a 3-way ball valve made of ABS/PVC
open
closed
1
Compressed air connection
2
3
‑
way ball valve
3
Pipe system
4
Air filter (optional)
5
TITANUS MICRO·SENS®
► Make sure that a compressed air supply is available at the 3-way ball
valve.
► Move the lever of the ball valve from the 90° setting (operating position)
to the 270° setting.
► Make sure that the TITANUS MICRO·SENS® is disconnected from the
pipe system to be purged.
► Purge the pipe system for 10 s.