MAN3186 - TITANUS MICRO
•
SENS®
63
4.2.6 Network module
Current consumption
All current consumptions specified refer to an ambient temperature of 20 °C
and a supply voltage of 24 V.
[mA]
Max. 50
Temperature range
4.3 Pipe system
Max. pipe length Ø 25 mm [m]
50
Max. number of aspiration apertures
8
Max. length of aspiration hose per
ceiling feed-through [m]
1
Temperature range [°C]
PVC pipe
-
10 … +60
ABS pipe
-
40 … +80
Max. monitoring area [m²]
500
[°C]
-
20 … +60
Deep freeze version [°C]
-
40 … +60