Risk of injury due to flammable liquids and vapours
Formation of explosive/highly flammable vapour/air mixtures is possible.
Injuries to health due to direct or indirect contact.
► Prior to processing, observe the safety notes of the manufacturer.
WARNING
6.17 Installation of aspiration
‑
reducing clips
Image 98:
Installation of aspiration
‑
reducing clips
Use aspiration
‑
reducing clips for refrigerated areas and when using air purge
systems. For all other applications, use aspiration
‑
reducing film sheets.
► Drill a hole with a 10 mm drill at right angles to the pipe.
► Deburr the drill hole carefully.
► Remove any shavings from the drilling area.
► Clean the drilling area along the entire pipe circumference to remove
any dirt and grease using Tangit cleaner.
► Select the size of the aspiration
‑
reducer according to the project
planning guidelines.
► Insert the aspiration
‑
reducer into a plastic clip for aspiration reducers
type AK-Cx.